SecuriStar MCD 573 X-S

FeaturesOperation/DescriptionsSpecifications
  • Combined smoke and temperature detector compliant with EN 54-5/7 
  • Optimal sensitivity thanks to Cubus levelling 
  • High false-alarm security thanks to temperature-supported smoke alarm evaluation

The MCD 573X is a hybrid fire detector: The temperature-supported smoke sensor provides early detection of smouldering, glowing and open fires with smoke development. Smoke sensitivity adapts to the prevailing ambient temperatures in the area and automatically regulates itself (Cubus levelling). The temperature sensor also detects fire with no smoke development when fires break out rapidly with high temperatures. The smoke detection system offers 2 programmable pre-signal levels. The temperature detection can be set to class A1, A2 or B, each combinable with the index S or R. The smoke and temperature alarms are signalled and parameterised separately. Self-monitoring, two-stage contamination display, and auto drift compensation guarantee optimal operability. Besides the programmable control output, the detector has a warning signal when ambient temperatures become too high.

Technical data  
24 VDC Operating voltage
17to 31 VDC Permitted voltage range
150 µA Operating current, quiescent (max.)
20 mA Operating current, alarm (max.)
EN 54-5 and 7 Standards
LED red Individual display
6,8 V/5 mA External display

-25°C to +60°C

10...95%

Ambient conditions

Operating temperature range

Short-term relative humidity

70% Constant relative humidity
IP 44 Protection class
White Colour
ABS/PC Housing material
125g Weight

 

Product summary  
MCD 573X Combined smoke and temperature detector
USB 501-1/-6 Universal SecuriStar base

SecuriStar MCD 573 X-SP

FeaturesOperation/DescriptionsSpecifications
  • Combined smoke and heat detector in compliance with EN 54-5/7/29 
  • Integrated sounder according to EN 54-3, volume up to 92 dB(A) 
  • Optimal sensitivity thanks to Cubus levelling 
  • High false-alarm security thanks to temperature-supported smoke alarm evaluation 
  • Integrated voice evacuation 
  • Uninterrupted audible alarm transmission

The MCD 573X-SP is a combined fire detector: the temperature-supported smoke sensor provides early detection of smouldering, glowing and open fires with smoke development. Smoke sensitivity adapts to the prevailing ambient conditions in the area and automatically regulates smoke sensitivity (Cubus levelling). The heat sensor also detects fires with no smoke development when fires break out rapidly with high temperatures. The smoke detection system provides two programmable pre-signal levels. Heat detection can be set to classes A1, A2 and B, each combinable with the index S or R. Smoke and heat can be evaluated either independently or as a combined algorithm (smoke and temperature). Optimum operability is guaranteed through self-monitoring, the two-stage contamination display, and alarm threshold tracking.

Technical data  
24 VDC Operating voltage
12to 31 VDC Permitted voltage range
150 µA Operating current, quiescent (max.)
20 mA Operating current, alarm (max.)
EN 54-3/5/7/29 Standards
LED red Individual display
5,0 V / 5 mA/1 mA/0,1mA External display
92/81/69 dB(A) Sounder volume
-25°C to +60°C

Ambient conditions

Operating temperature range

10...95% Short-term relative humidity
70% Constant relative humidity
White Colour
ABS/PC Housing material
133g Weight

 

Product summary  
MCD 573X-SP Combined smoke and heat detector with integrated sounder and voice evacuation
MCD 573X-SPCT Combined smoke and heat detector with integrated sounder and voice evacuation for uninterruptible alerting
USB 501-1/-6 Universal SecuriStar base

SecuriStar MCD 573 X

FeaturesOperation/DescriptionsSpecifications
  • Combined smoke and temperature detector according to EN 54-5/7/29 
  • Integrated acoustics according to EN 54-3, volume up to 92 dB(A) 
  • Optimal sensitivity thanks to Cubus levelling 
  • High false-alarm security thanks to temperature-supported smoke-alarm evaluation

The MCD 573X-S is a combined fire detector: the temperature-supported smoke sensor provides early detection of smouldering, glowing and open fires with smoke development. Smoke sensitivity adapts to the prevailing ambient conditions in the area and automatically regulates itself (Cubus levelling). The heat sensor also detects fires with no smoke development when fires break out rapidly with high temperatures. The smoke detection system provides two programmable pre-signal levels. Heat detection can be set to classes A1, A2 and B, each combinable with the index S or R. The two criteria smoke and temperature can be evaluated either independently or as a combined algorithm for smoke and temperature. Optimum operability is guaranteed through self-monitoring, the two-stage contamination display, and alarm threshold tracking.

Technical data  
24 VDC Operating voltage
12to 31 VDC Permitted voltage range
150 µA Operating current, quiescent (max.)
20 mA Operating current, alarm (max.)
EN 54-3/5/7/29 Standards
LED red Individual display
5,0 V / 5 mA/1 mA/0,1mA External display
92/81/69 dB(A) Sounder volume
-25°C to +60°C

Ambient conditions

Operating temperature range

10...95% Short-term relative humidity
70% Constant relative humidity
White Colour
ABS/PC Housing material
133g Weight

 

Product summary  
MCD 573X-S Combined smoke and heat detector with integrated sounder
USB 501-1/-6 Universal SecuriStar base
`

SecuriStar CCD 573 X

FeaturesOperation/DescriptionsSpecifications
  • Combined smoke, heat and carbon monoxide (CO) detector according EN 54-5/7/26/29/30 
  • Optimal sensitivity 
  • False-alarm security through temperature supported smoke alarm evaluation (Cubus levelling) and temperature and carbon monoxide-supported smoke alarm evaluation (Cubus+ levelling)
  • Technical CO alarm according EN 50291-1 
  • Adjustable technical CO pre-signal 20…320 ppm

The CCD 573X is a combined fire detector: The temperature- and CO-supported smoke sensor provides early detection of smouldering, glowing and open fires with smoke development. The smoke sensitivity adapts to the prevailing ambient conditions in the area. The detector automatically regulates the smoke sensitivity based on the temperature and CO content (Cubus and Cubus+ levelling). The temperature sensor even detects fire with no smoke development when fires spread rapidly at high temperatures. The smoke detection system offers 2 programmable pre-signal stages. The temperature detection can be set to class A1, A2 or B, each combinable with the index S or R. The CO cell detects the rise in carbon monoxide gas released during fires. The three criteria of smoke, heat and CO can be evaluated either independently or as combined algorithms for smoke and temperature or CO and temperature. Self-monitoring, two-stage contamination display and alarm threshold monitoring guarantee optimal operability.

Technical data  
24 VDC Operating voltage
7 to 31 VDC Permitted voltage range
150 µA Operating current, quiescent (max.)
20 mA Operating current, alarm (max.)
EN 54-5/7/26/29/30 Standards
LED red Individual display

5,0 V

5 mA/1 mA/0,1mA

External display, programmable control output

Ambient conditions

-25°C to +60°C Operating temperature range
15...90% relative humidity, ≤34°C
IP 40 Protection class
White Colour
ABS/PC Housing material
Yellow Marking
125g Weight
7 Years Service life
8 Years Duration of life
G 212187 VdS approval
0786-GPD-21215 CPD approval

 

Product summary  
CCD 573X Combined smoke, heat and CO detector
USB 501-1/-6 Universal SecuriStar base

PHOTO GALLERY

FOLLOW US